How to use the radiator size calculator
- Pick the Room type, then type in the Room length, Room width and Ceiling height.
- Fill in the outside walls, External wall type, windows, Glazing, and what is above and below the room. Add Where are you? and How draughty is the house? to finish the room details.
- Choose your Heating system: older boiler (75/65), modern condensing boiler (70/50), heat pump (50/40), low-temperature heat pump (45/35), or My own temperatures if you know your flow and return.
- If more than one radiator will heat the room, set Number of radiators in the room. We split the output equally between them.
- Read the Radiator output needed, in BTU/h and watts at ΔT 50. This is the figure to match to the catalogue. Pick the next size up.
- Tap Add to shopping list to keep it, or Share link to send it to your installer.
Why use this calculator
It corrects for your water temperature. A catalogue radiator is rated at one test condition. If your boiler or heat pump runs cooler, the radiator gives out less heat. This calculator works out how much bigger you need to go, so you don't end up with a room that stays cold.
It starts from your room, not a guess. It uses the same room heat-loss method as our BTU calculator, so walls, windows, roof, floor and draughts all count.
It is neutral. It gives you the output to look for, not a product to buy. You can use the figure to compare radiators from any shop or maker.
It shows the working, including the correction factor, so you can check it or hand it to your installer.
How we worked it out
Your numbers, step by step. This updates as you change the calculator.
- Room: 4.5 m × 3.5 m × 2.4 m high = 37.8 m³ (floor 15.75 m²).
- Temperature difference (ΔT): we aim for 21 °C in a living room and plan for -3 °C outside in a typical UK location, so ΔT = 21 − (-3) = 24 K.
- External wall area: (4.5 + 3.5) m × 2.4 m = 19.2 m². Minus 2.4 m² of windows leaves 16.8 m² of wall.
- Walls: U 1.5 W/m²K (cavity wall, not insulated) × 16.8 m² × 24 K = 605 W.
- Windows: U 2 W/m²K (double glazing, 2002 to 2021) × 2.4 m² × 24 K = 115 W.
- Ceiling: the room above is heated, so we count 0 W.
- Floor: U 0.8 W/m²K (solid ground floor) × 15.75 m² × 24 K = 302 W.
- Air: 0.33 × 1.5 air changes per hour × 37.8 m³ × 24 K = 449 W.
- Total heat loss = 605 + 115 + 0 + 302 + 449 = 1,471 W (1.47 kW).
- Convert to BTU/h: 1,471 W × 3.412 = 5,021 BTU/h, rounded to the nearest 50 = 5,000 BTU/h.
- Water temperature: (flow 70 + return 50) ÷ 2 = 60 °C on average.
- Radiator ΔT = average water temperature − room temperature = 60 − 21 = 39 K.
- Catalogue outputs are quoted at ΔT 50. At ΔT 39 a radiator gives 0.724 of its catalogue output (interpolated from the standard table; based on output ∝ ΔT^1.3).
- Catalogue (ΔT 50) output needed = 1,471 W ÷ 0.724 = 2,032 W, which is 6,933 BTU/h. Rounded up: 2,040 W or 6,950 BTU/h.
The formula
First we work out the room’s heat loss in watts, using the same method as the BTU calculator: fabric loss (U-value × area × temperature difference for walls, windows, ceiling and floor) plus air loss (0.33 × air changes per hour × volume × temperature difference).
Then we correct it for the radiator’s water temperature:
- Mean water temperature = (flow + return) ÷ 2.
- Radiator ΔT = mean water temperature − room temperature.
- Output factor for that ΔT, from the table below.
- Catalogue output needed = room heat loss ÷ output factor.
- Round up to the next 10 W, and the next 50 BTU/h (watts × 3.412).
What is ΔT50, and why does the factor matter?
Radiators in catalogues are rated at ΔT 50. That is the standard test condition: the average water temperature 50 °C above the room. A radiator running cooler gives out less. The output goes up and down with ΔT to the power 1.3, and manufacturers publish the result as a table. We use the same table and fill the gaps in between.
| ΔT (K) | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
|---|---|---|---|---|---|---|---|---|---|
| Output factor | 0.304 | 0.406 | 0.515 | 0.629 | 0.748 | 0.872 | 1.000 | 1.132 | 1.267 |
At ΔT 30 a radiator gives about half its catalogue output, so you need one about twice the size.
What the systems mean for a 21 °C living room
| Heating system | Flow / return | ΔT | Output factor |
|---|---|---|---|
| Older boiler | 75 / 65 | 49 K | 0.974 |
| Modern condensing boiler | 70 / 50 | 39 K | 0.724 |
| Heat pump | 50 / 40 | 24 K | 0.386 |
| Low-temperature heat pump | 45 / 35 | 19 K | 0.285 |
For our default living room (about 1,470 W of heat loss), that means a catalogue radiator of about 5,200 BTU/h with an older boiler, 6,950 BTU/h with a condensing boiler, 13,050 BTU/h with a 50/40 heat pump and 17,650 BTU/h with a 45/35 heat pump. A bedroom is kept at 18 °C, so the same system has a bigger ΔT there.
What we assume
- Room temperatures, outside design temperatures, air changes and U-values are the same as the BTU calculator.
- The output factor follows the manufacturer table above, and above ΔT 75 we extend it with the same formula (ΔT to the power 1.3).
- With more than one radiator, we split the output equally between them.
- This is a guide. Check with your installer or a Gas Safe engineer before changing a heating system. A full heat-loss survey is the proper way to size a new system.
Tips
- Check the catalogue figure is rated at ΔT 50. Some catalogues also list lower ΔT figures, which are smaller numbers, and comparing the wrong ones makes a radiator look too small or too big.
- Round up to the next size, but don't go much bigger. A radiator that is a little big is fine. A radiator that is too small never warms the room.
- If you are fitting a heat pump, expect bigger radiators in most rooms, or underfloor heating in some. A heat pump installer should design the whole system, so use this to check what they propose.
- Two smaller radiators can suit a big room better than one large one, for example under two windows. Set the number of radiators to see the size of each.
- Don't change boiler flow temperatures yourself. Ask a Gas Safe engineer to set them.